CVE-2017-7574

9.8 CRITICAL
Published: April 06, 2017 Modified: May 29, 2026
View on NVD

Description

Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product.

AI Explanation

Get an AI-powered plain-language explanation of this vulnerability and remediation steps.

Login to generate AI explanation

CVSS v3.x Details

0.0 Low Medium High Critical 10.0
Vector String
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H

References to Advisories, Solutions, and Tools

Patch Vendor Advisory Exploit Third Party Advisory
http://www.securityfocus.com/bid/97518
Source: cve@mitre.org
Third Party Advisory VDB Entry
https://os-s.net/advisories/OSS-2017-02.pdf
Source: cve@mitre.org
Broken Link
http://download.schneider-electric.com/files?p_Doc_Ref=SEVD-2017-097-01
Source: af854a3a-2127-422b-91ae-364da2661108
Vendor Advisory
http://www.securityfocus.com/bid/97518
Source: af854a3a-2127-422b-91ae-364da2661108
Third Party Advisory VDB Entry
https://os-s.net/advisories/OSS-2017-02.pdf
Source: af854a3a-2127-422b-91ae-364da2661108
Broken Link

6 reference(s) from NVD

Quick Stats

CVSS v3 Score
9.8 / 10.0
EPSS (Exploit Probability)
1.2%
65th percentile
Exploitation Status
Not in CISA KEV

Weaknesses (CWE)

Affected Vendors

schneider-electric